精品国产乱码久久久久久狼|亚洲无码99亚洲激情一级片|日韩av有码无码不卡五区|欧美日韩一级黄片手机免费在线观看

PRODUCT

ENTERPRISE BRIEF INTRODUCTION

HKXB-600 Box Variable Measurement & Control Device

PRODUCT OVERVIEW

HKXB-600 box variable measurement and control device is used in new energy power stations(photovoltaic power stations,wind farms,etc),providing protection,measurement and control,protocol conversion,ring network communication and other functions for each on-site power generation unit,The device can be installed in a group screen or directly in a step-up box substation(non-direct grounding system or small resistance grounding system with voltage level of 35kv and below etc,) in the power generation unit.

KEY FEATURE

  • It adopts high-performance 32-bit high-speed DSP monolithic digital signal processing controller as the main control unit
  • The software and hardware are modular design,the hardware module adopts the internal LAN,and the design mode of the intelligent node can be flexibly configured,which greatly improves the reliability of the device
  • High-speed floating-point arithmetic is used to greatly improve the measurement accuracy.The protection current measurement error is less than ±%,and the measurement current error is less than ±0.5%.
  • The operation time is greater than 1000mS.The error is less than ±2%,the action time is less than 1000mS,and the error is less than ±20mS
  • Full AC sampling and software digital filtering completely eliminate the influence of ero drift of the hardware circuit.
  • The display module has a friendly man-machine interface,and all interface are displayed with needed languish,which is convenient to operate.
  • All measured and parameters can be displayed in real time via the display module
  • All critical data (system parameters,etc.) can be stored for more than ten years in the event of a power loss.
  • Perfect accident record and self-inspection function,convenient for users to analyze the cause of the accident.It can record 100 protection action events,100 
  • alarm events,and 100 displacement events.
  • The device adopts fully sealted embedded structure,software and hardware redundancy design,perfect software and hardware self-test,strong anti-interference performance
  • Easy debugging and maintenance,with friendly man-machine interface and right PC auxiliary software,convenient for device setup and debugging.

  

Rated Frequency

50Hz

Rated Current

5A/1A

Linear Range

0.05In 20In

Continuous Overload Capacity 2In

1s Overload Capacity

20In

Power Consumption

>0.25VA/phase (rated current)

Alternating Current Voltage 

 

Rated Frequency

50Hz

Rated Voltage

380V(common,phase to phase),or 690V(inter phase)

Linear Range

3.8  540V

Continuous Overload Capacity 560V(relative)
10s Overload Capacity 590V(relative)

1s Overload Capacity

600V(relative)

Power Consumption

>0.5VA/phase(rated voltage)

DC Power Supply

 

Rated Voltage

220Vdc

Input Range

86  264Vdc

 Ripple

≤ 15% of rated voltage

 Static Power Consumption

<15W

Acting Power Consumption

<20W

DC Polarity Reverse Connection

Normal Working

AC Power Supply

 

Rated Voltage

220Vac

Input Range

86  264Vdc

 Static Power Consumption

<15W

Acting Power Consumption

<20W

Switch Value Input

   DC110Vd 

220Vdc 220V(AC)

Rated Voltage

   80

160 160

Starting Voltage

   3mA

4mA 4mA

Rated Current

(Model Value)

   126.5

253 253

Withstand Voltage Level

2000Vac, 2800(Vdc)

Switch Value Output

 

Output Contact Classification

Trip, Signal

Output Mode

 Passive contact

Max Working Voltage

 380Vac,250Dac

Touch Point Withstand

 1000V RMS,1minute

Continuous Current Carrying Capacity

 5A

Impact Over Current Capacity

8A@3s

12A@1s 

16A@0.5s 

30A@0.2s

Arc Breaking Capacity(L/R=40ms)

0.65A@48Vdc

0.35A@110Vdc 0.20A@220Vdc 0.15A@250Vdc

Acting Capacity

<8ms

Returning Time

<5ms

Working Life

10000 times

Remote Measurement Grade

 

Voltage/Current/Frequency

0.5

Other

1.0

Time Interface

 

Transmitting Distance

<500m

Max Load Capacity

32

Time Interface Standard

Pulse/s IRIG-B

Contact Mode

RS485

Machenical Structure

 

Box Structure

6U

Color

Silver Gray

Weight

5kg

Pollution Grade

2

Protection Level

Front board: IP50

Side board:IP30

Back board: IP10(GB4208 2008)

Environment

 

Working Temperature Range

-40℃~+70℃

Short Working Temperature Range

-40℃~+80℃<16h;

Note:

Man-machine interface performance will be downward;

Once working temperature exceeded

Storage Temperature

-40℃~+80℃

Humidity

5%-95% No condensation or Frozen

 

 

 

                                                     

         

                                                              

HKXB-600 Box Variable Measurement & Control Device